N2XSEYFGbY 3,6/6 kV, 6/10 kV, 18/30 kV, 19/33 kV

Copper core, XLPE insulated, armoured, 3-cores

Konstrukce

  • Circular bare copper core stranded according to IEC 60228
  • Inner semi-conductive layer
  • Core insulation XLPE
  • Color code according to HD 308 S2
  • Outer semi-conductive layer
  • Semi-conductive layer
  • Copper tape screen
  • Filler
  • PVC inner sheath
  • Galvanized steel wire armour (SWA)
  • Galvanized steel tape
  • PVC outer sheath (red or black)

Technická data

  • Power cable according to DIN VDE 0276 part 603, HD 620, IEC 60502, BS 6622
  • Temperature range max. to +90 °C
  • Temperature from 0 °C to +70 °C
  • Short circuit temperature +250 °C (up to 5 seconds)
  • Nominal voltage Uo/U 3,6/6 kV, 6/10 kV, 6,35/11 kV (dle BS), 18/30 kV, 19/33 kV (dle BS)
  • Operating voltages for 3,6/6 kV = max. 7,2 kV
    6/10 kV = max. 12 kV
    18/30 kV = max. 36 kV
  • Test voltage a.c. for 3,6/6 kV = 11 kV up to 5 min.
    6/10 kV = 21 kV up to 5 min.
    18/30 kV = 63 kV up to 5 min.
  • Minimum bending radius approx. 15 x cable diameter

Použití

These power armoured cables are designed for open air installation, for direct burrial underground, in water, in cable ducts, power stations, where mechanical damages to the cable may occur.

Note

  • Voltage 12/20 kV on request.
  • Halogenfree version on request.

Technické parametry

2XSEYFGbY 3,6/6 kV

SKU Počet žil x průřez jádra [mm²] Vnější ø cca [mm] Činný odpor jádra (ohm/km) Indukčnost (mH/km) Kapacita (uF/km) Hmotnost kabelu [kg/km] Proudové zatížení v zemi při 20°C (A) Proudové zatížení ve vzduchu při 30°C (A)
09343391 3×25/16 44.5 0.7270 0.370 0.208 3400 149 141
09343401 3×35/16 47.0 0.5240 0.352 0.229 3950 176 171
09343411 3×50/16 50.5 0.3870 0.336 0.255 4700 208 196
09343421 3×70/16 54.5 0.2680 0.318 0.288 5650 255 249
09343431 3×95/16 58.5 0.1930 0.303 0.324 6750 307 307
09343441 3×120/16 63.0 0.1530 0.292 0.359 8000 353 353
09343451 3×150/25 66.0 0.1240 0.284 0.388 9200 396 406
09343461 3×185/25 70.0 0.0991 0.276 0.424 10650 447 464
09343471 3×240/25 77.5 0.0754 0.267 0.469 13100 523 548
09343481 3×300/25 84.0 0.0601 0.263 0.486 15700 581 632
09343491 3×400/35 93.0 0.0470 0.257 0.521 19750 653 726

N2XSEYFGbY 6/10 kV

SKU Počet žil x průřez jádra [mm²] Vnější ø cca [mm] Činný odpor jádra (ohm/km) Indukčnost (mH/km) Kapacita (uF/km) Hmotnost kabelu [kg/km] Proudové zatížení v zemi při 20°C (A) Proudové zatížení ve vzduchu při 30°C (A)
09343392 3×25/16 49.5 0.7270 0.392 0.173 3950 148 143
09343402 3×35/16 52.0 0.5240 0.374 0.189 4450 178 173
09343412 3×50/16 54.5 0.3870 0.355 0.209 5200 210 206
09343422 3×70/16 58.5 0.2680 0.336 0.236 6200 256 257
09343432 3×95/16 63.0 0.1930 0.320 0.263 7400 307 313
09343442 3×120/16 67.0 0.1530 0.308 0.291 8600 349 360
09343452 3×150/25 70.5 0.1240 0.299 0.314 9850 392 410
09343462 3×185/25 74.5 0.0991 0.290 0.341 11350 443 469
09343472 3×240/25 81.5 0.0754 0.278 0.387 13850 513 553
09343482 3×300/25 87.0 0.0601 0.270 0.422 16250 576 635
09343492 3×400/35 94.5 0.0470 0.261 0.475 20150 650 731

hN2XSEYFGbY 18/30 kV, dle BS 19/33 kV

SKU Počet žil x průřez jádra [mm²] Vnější ø cca [mm] Činný odpor jádra (ohm/km) Indukčnost (mH/km) Kapacita (uF/km) Hmotnost kabelu [kg/km] Proudové zatížení v zemi při 20°C (A) Proudové zatížení ve vzduchu při 30°C (A)
09343404 3×35/16 74.5 0.5240 0.457 0.114 7850
09343414 3×50/16 78.0 0.3870 0.434 0.124 8750 214 217
09343424 3×70/16 81.5 0.2680 0.410 0.137 9950 261 269
09343434 3×95/16 85.5 0.1930 0.389 0.150 11250 313 326
09343444 3×120/16 89.5 0.1530 0.372 0.163 12600 356 377
09343454 3×150/25 93.0 0.1240 0.360 0.174 14000 400 426
09343464 3×185/25 97.0 0.0991 0.348 0.188 15700 441 488
09343474 3×240/25 104.0 0.0754 0.331 0.209 18500 510 576
09343484 3×300/25 109.5 0.0601 0.321 0.226 21150 604 651