Marking for harmonized cables

according to DIN VDE 0281, 0282, 0292

H 07 R C N D3 – F – 5 G 1,5

Identification of marking

  • A – approved national type
  • H – harmonized type

Nominal voltage

  • 01 – 100V
  • 03 – 300/300V
  • 05 – 300/500V
  • 07 – 450/750V

Insulation material

  • B – (EPR) Ethylene-propylene rubber
  • G – (EVA) Ethylene-vinyl acetate copolymer
  • N2 – (CR) Chloroprene rubber for welding cables
  • R – (NR or SR) Natural or synthetic rubber
  • S – (SiR) Silicone rubber
  • V – (PVC) Polyvinyl chloride
  • V2 – (PVC) Polyvinylchlorid teplotně odolný
  • V3 – (PVC) Polyvinyl chloride heat resistant
  • V4 – (PVC) Polyvinyl chloride cross-linked
  • Z – (PE) Polyethylene cross-linked

Construction elements

  • C – Screening
  • Q4 – (PA) Additional polyamide core wrap
  • T – Additional textile braiding of all cores
  • T6 – Additional textile braiding of single cores

Sheath material

  • B – (EPR) Ethylene-propylene rubber
  • J – Fibre optic braiding
  • N – (CR) Chloroprene rubber
  • N2 – (CR) Chloroprene rubber for welding cables
  • N4 – (CR) Chloroprene rubber heat resistant
  • Q – (PUR) Polyurethan
  • R – (NR or SR) Natural or synthetic rubber
  • T – Textile braiding
  • T2 – Textile braiding with self-extinguishing substance
  • V – (PVC) Polyvinyl chloride
  • V2 – (PVC) Polyvinyl chloride heat resistant
  • V3 – (PVC) Polyvinyl chloride for low temperatures
  • V4 – (PVC) Polyvinyl chloride cross-linked
  • V5 – (PVC) Polyvinyl chloride oil resistant

Special construction characteristics

  • D3 – Elements for tension relief of the cable (bearing conductor)
  • D5 – Middle core (without bearing element)
  • FM – Telecommunication cores integrated to power cables
  • H – Flat, separable cable (twin cable)
  • H2 – Flat, unseparable cable (sheated cable with two cores)
  • H6 – Flat, unseparable cable (cable with multiple sheating)
  • H7 – Two-layer sheath
  • H8 – Spiral cable

Cable type

  • D – Fine stranded for welding cables
  • E – (Extra) fine stranded for welding cables
  • F – Stranded for cables for fixed installation
  • H – (Extra) fine stranded for flexible cables
  • K – Stranded for cables for fixed installation
  • R – Stranded core rounded, class 2
  • U – Plain wire rounded, class 1
  • Y – Leon core to DIN 47104

No. of cores

Earth core

  • G – With earth core
  • X – Without earth core

Core cross-section